Uses National Foam Concentrates Aer-O-Lite 3% and Aer-O-Water 3EM 3%, only, at a 2 percent concentration for hydrocarbon fuel applications. Uses Ansul, Incorporated Ansulite 3X3 LV alcohol resistant concentrate, only, at a 6 percent concentration for alcohol and ketone fuel applications. For use only with FireFlex ARC-1 or Notifier NFC-320/E/C release control panels.
Discharge may be initiated either manually, electrically, electrically in a failsafe mode, or pneumatically. Requires a reliable water supply pressure between 50 and 175 psi (3.5 and 12.1 bar) at the required system flow. Compressed air is supplied by cylinders at 2400 psi (165.5 bar). Includes concentrate supply tank. Provides a minimum of 10 minutes of discharge with the option to provide a second 10 minutes, to be either manually or automatically activated, if required.
Uses FireFlex TAR 225C nozzles at a maximum area of coverage of 150 ft2 (13.9 m2 ) for hydrocarbon fuel applications and 100 ft2 (9.3 m2 ) for alcohol and ketone fuel applications and TAR 225L nozzles for applications where a three dimensional fire requires horizontal discharge.
Minimum ceiling height is 8 ft (2.4 m) and maximum nozzle height is 46 ft (14 m) for hydrocarbon fuel applications and 35 ft (10.7 m) for alcohol and ketone fuel applications.
FPO (Foam Powered Oscillating) nozzles are available for use where flammable liquid spills occur on horizontal surfaces and may cause pool fires. They are designed to provide discharge over the specified angles and ranges of coverage shown from a 2 ft (0.6 m) minimum height above floor level.